| Sign In | Join Free | My futurenowinc.com |
|
Brand Name : SIEMENS
Model Number : 6ES7511-1CK00-0AB0
Certification : CE
Place of Origin : Germany
MOQ : 1
Price : USD
Payment Terms : L/C, T/T
Supply Ability : 100
Delivery Time : 10-12Days
Packaging Details : 15,10 x 15,40 x 4,60
SIEMENS 6ES7511-1CK00-0AB0 PROFINET IRT WITH 2-PORT SWITCH, 60 NS BIT PERFORMANCE, INCL. PUSH-IN FRONT CONNECTOR, SIMAT
The SIEMENS 6ES7511-1CK00-0AB0 is a central processing unit (CPU) that is part of the SIMATIC S7-1500 automation system. Here are the key details about this CPU:
PROFINET IRT with 2-Port Switch:
- This CPU has a built-in PROFINET interface with an integrated 2-port switch.
- The PROFINET interface supports the PROFINET IRT (Isochronous Real-Time) communication protocol, which enables highly synchronized and deterministic data exchange.
- The 2-port switch allows the CPU to be connected directly to other PROFINET devices without requiring an external switch.
Fast 60 ns Bit Performance:
- This CPU has a bit performance of 60 nanoseconds per bit operation.
- While not as fast as some higher-end S7-1500 CPUs, the 60 ns bit performance still provides very responsive control capabilities.
Push-In Front Connector:
- The CPU comes with a push-in front connector for the PROFINET interface.
- This push-in connector provides a convenient and tool-free way to connect PROFINET cables to the CPU.
SIMATIC Memory Card Required:
- Like other SIMATIC S7-1500 CPUs, this model requires a SIMATIC memory card to be inserted for operation.
- The memory card provides storage for the user program, configuration data, and other runtime information.
Other Features:
- Work Memory: 300 KB for program and 1 MB for data
- Part of the modular SIMATIC S7-1500 system
- Programmed using the STEP 7 engineering software
The key distinguishing features of this CPU model are the integrated PROFINET IRT interface with a 2-port switch, the fast 60 ns bit performance, and the push-in front connector.
These capabilities make the CPU 1511-1 PN a good choice for applications that require highly synchronized and deterministic industrial Ethernet communication, but may not need the extreme processing speeds of higher-end S7-1500 CPUs.
The 2-port switch and push-in connector provide convenient connectivity options, while the 60 ns bit performance still delivers responsive control for many industrial automation tasks.
Overall, the 6ES7511-1CK00-0AB0 is a versatile and capable CPU within the SIMATIC S7-1500 portfolio, well-suited for a wide range of industrial automation applications.
| General information | ||
| Product type designation | CPU 1511C-1 PN | |
| HW functional status | FS03 | |
| Firmware version | V2.9 | |
| Product function | ||
| ● I&M data | Yes; I&M0 to I&M3 | |
| ● Isochronous mode | Yes; With minimum OB 6x cycle of 625 µs (distributed) | |
| Engineering with | ||
| ● STEP 7 TIA Portal configurable/integrated from version | V17 (FW V2.9) / V13 SP1 Update 4 (FW V1.8) or higher | |
| Configuration control | ||
| via dataset | Yes | |
| Display | ||
| Screen diagonal [cm] | 3.45 cm | |
| Control elements | ||
| Number of keys | 6 | |
| Mode selector switch | 1 | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V; 20.4 V DC, for supplying the digital inputs/outputs | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes | |
| Mains buffering | ||
| ● Mains/voltage failure stored energy time | 5 ms; Refers to the power supply on the CPU section | |
| Input current | ||
| Current consumption (rated value) | 0.8 A; Digital onboard I/O modules are supplied separately | |
| Inrush current, max. | 1.9 A; Rated value | |
| I²t | 0.34 A²·s | |
| Digital inputs | ||
| ● from load voltage L+ (without load), max. | 20 mA; per group | |
| Digital outputs | ||
| ● from load voltage L+, max. | 30 mA; Per group, without load | |
| output voltage / header | ||
| Rated value (DC) | 24 V | |
| Encoder supply | ||
| Number of outputs | 1; One common 24 V encoder supply | |
| 24 V encoder supply | ||
| ● 24 V | Yes; L+ (-0.8 V) | |
| ● Short-circuit protection | Yes | |
| ● Output current, max. | 1 A | |
| Power | ||
| Infeed power to the backplane bus | 10 W | |
| Power consumption from the backplane bus (balanced) | 8.5 W | |
| Power loss | ||
| Power loss, typ. | 11.8 W | |
| Memory | ||
| Number of slots for SIMATIC memory card | 1 | |
| SIMATIC memory card required | Yes | |
| Work memory | ||
| ● integrated (for program) | 175 kbyte | |
| ● integrated (for data) | 1 Mbyte | |
| Load memory | ||
| ● Plug-in (SIMATIC Memory Card), max. | 32 Gbyte | |
| Backup | ||
| ● maintenance-free | Yes | |
| CPU processing times | ||
| for bit operations, typ. | 60 ns | |
| for word operations, typ. | 72 ns | |
| for fixed point arithmetic, typ. | 96 ns | |
| for floating point arithmetic, typ. | 384 ns | |
| CPU-blocks | ||
| Number of elements (total) | 4 000; Blocks (OB, FB, FC, DB) and UDTs | |
| DB | ||
| ● Number range | 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 | |
| ● Size, max. | 1 Mbyte; For DBs with absolute addressing, the max. size is 64 KB | |
| FB | ||
| ● Number range | 0 ... 65 535 | |
| ● Size, max. | 175 kbyte | |
| FC | ||
| ● Number range | 0 ... 65 535 | |
| ● Size, max. | 175 kbyte | |
| OB | ||
| ● Size, max. | 175 kbyte | |
| ● Number of free cycle OBs | 100 | |
| ● Number of time alarm OBs | 20 | |
| ● Number of delay alarm OBs | 20 | |
| ● Number of cyclic interrupt OBs | 20; With minimum OB 3x cycle of 500 µs | |
| ● Number of process alarm OBs | 50 | |
| ● Number of DPV1 alarm OBs | 3 | |
| ● Number of isochronous mode OBs | 1 | |
| ● Number of technology synchronous alarm OBs | 2 | |
| ● Number of startup OBs | 100 | |
| ● Number of asynchronous error OBs | 4 | |
| ● Number of synchronous error OBs | 2 | |
| ● Number of diagnostic alarm OBs | 1 | |
| Nesting depth | ||
| ● per priority class | 24 | |
| Counters, timers and their retentivity | ||
| S7 counter | ||
| ● Number | 2 048 | |
| Retentivity | ||
| — adjustable | Yes | |
| IEC counter | ||
| ● Number | Any (only limited by the main memory) | |
| Retentivity | ||
| — adjustable | Yes | |
| S7 times | ||
| ● Number | 2 048 | |
| Retentivity | ||
| — adjustable | Yes | |
| IEC timer | ||
| ● Number | Any (only limited by the main memory) | |
| Retentivity | ||
| — adjustable | Yes | |
| Data areas and their retentivity | ||
| Retentive data area (incl. timers, counters, flags), max. | 128 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 88 KB | |
| Extended retentive data area (incl. timers, counters, flags), max. | 1 Mbyte; When using PS 6 0W 24/48/60 V DC HF | |
| Flag | ||
| ● Size, max. | 16 kbyte | |
| ● Number of clock memories | 8; 8 clock memory bit, grouped into one clock memory byte | |
| Data blocks | ||
| ● Retentivity adjustable | Yes | |
| ● Retentivity preset | No | |
| Local data | ||
| ● per priority class, max. | 64 kbyte; max. 16 KB per block | |
| Address area | ||
| Number of IO modules | 1 024; max. number of modules / submodules | |
| I/O address area | ||
| ● Inputs | 32 kbyte; All inputs are in the process image | |
| ● Outputs | 32 kbyte; All outputs are in the process image | |
| per integrated IO subsystem | ||
| — Inputs (volume) | 8 kbyte | |
| — Outputs (volume) | 8 kbyte | |
| per CM/CP | ||
| — Inputs (volume) | 8 kbyte | |
| — Outputs (volume) | 8 kbyte | |
| Subprocess images | ||
| ● Number of subprocess images, max. | 32 | |
| Hardware configuration | ||
| Number of distributed IO systems | 32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link) | |
| Number of DP masters | ||
| ● Via CM | 4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total | |
| Number of IO Controllers | ||
| ● integrated | 1 | |
| ● Via CM | 4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total | |
| Rack | ||
| ● Modules per rack, max. | 32; CPU + 31 modules | |
| PtP CM | ||
| ● Number of PtP CMs | the number of connectable PtP CMs is only limited by the number of available slots | |
| Time of day | ||
| Clock | ||
| ● Type | Hardware clock | |
| ● Backup time | 6 wk; At 40 °C ambient temperature, typically | |
| ● Deviation per day, max. | 10 s; Typ.: 2 s | |
| Operating hours counter | ||
| ● Number | 16 | |
| Clock synchronization | ||
| ● supported | Yes | |
| ● in AS, master | Yes | |
| ● in AS, slave | Yes | |
| ● on Ethernet via NTP | Yes | |
| Digital inputs | ||
| integrated channels (DI) | 16 | |
| Digital inputs, parameterizable | Yes | |
| Source/sink input | P-reading | |
| Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
| Digital input functions, parameterizable | ||
| ● Gate start/stop | Yes | |
| ● Capture | Yes | |
| ● Synchronization | Yes | |
| Input voltage | ||
| ● Type of input voltage | DC | |
| ● Rated value (DC) | 24 V | |
| ● for signal "0" | -3 to +5V | |
| ● for signal "1" | +11 to +30V | |
| Input current | ||
| ● for signal "1", typ. | 2.5 mA | |
| Input delay (for rated value of input voltage) | ||
| for standard inputs | ||
| — parameterizable | Yes; none / 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms | |
| — at "0" to "1", min. | 4 µs; for parameterization "none" | |
| — at "0" to "1", max. | 20 ms | |
| — at "1" to "0", min. | 4 µs; for parameterization "none" | |
| — at "1" to "0", max. | 20 ms | |
| for interrupt inputs | ||
| — parameterizable | Yes; Same as for standard inputs | |
| for technological functions | ||
| — parameterizable | Yes; Same as for standard inputs | |
| Cable length | ||
| ● shielded, max. | 1 000 m; 600 m for technological functions; depending on input frequency, encoder and cable quality; max. 50 m at 100 kHz | |
| ● unshielded, max. | 600 m; for technological functions: No | |
| Digital outputs | ||
| Type of digital output | Transistor | |
| integrated channels (DO) | 16 | |
| Current-sourcing | Yes; Push-pull output | |
| Short-circuit protection | Yes; electronic/thermal | |
| ● Response threshold, typ. | 1.6 A with standard output, 0.5 A with high-speed output; see manual for details | |
| Limitation of inductive shutdown voltage to | -0.8 V | |
| Controlling a digital input | Yes | |

|
|
SIEMENS 6ES7511-1CK00-0AB0 PROFINET IRT WITH 2-PORT SWITCH, 60 NS BIT PERFORMANCE, INCL. PUSH-IN FRONT CONNECTOR, SIMAT Images |